FF-series Fire Fighting Pumps
-
FF-XA
Fire Pump -
FF-XA
Fire Pump -
FF-XA
Fire Pump -
FF-XA
Fire Pump -
FF-XA
Fire Pump(+Expansion Joint) -
FF-XA
Fire Pump(+Expansion Joint)
-
FF-XA Customized
Fire Pump(Without Pressure Tank) -
FF-XA Customized
Fire Pump(Without Pressure Tank) -
FF-XA Customized
Fire Pump(Without Pressure Tank) -
FF-XA Customized
For Relay station in high-rising building
-
FF+JP(ECDL)
Fire Pump with Jockey Pump(ECDL type) -
FF+JP(WZ)
Fire Pump with Jockey Pump(WZ type) -
FF+JP(WZ)
Fire Pump with Jockey Pump(WZ type) -
FF+JP(WZ)
Fire Pump with Jockey Pump(WZ type) -
FF+JP(HDP)
Fire Pump with Jockey Pump(HDP type) -
FF+JP(HDP)
Fire Pump with Jockey Pump(HDP type)
-
FF-ECDL (Customized)
Main pump uses ECDL Vertical Multi-stage Pump -
FF-ESS (Customized)
Main pump uses ESS Split-casing Pump -
FFE-XA (Customized)
Fire Pump (Diesel Engine driven) -
FFE-XA (Customized)
Fire Pump (Diesel Engine driven) Outdoor Type
Features
1.Pump
Adopting XA model End suction single stage centrifugal pump
1.1 In accordance with DIN24255(EN733) standard.
2.Back-pull-out design for easily repairing.
3.Shaft sealing with mechanical seal.
4. diverse material options of pump casing, shaft, and impeller.
5. 42 different sizes in the range, 6.Capacity:1080M3/hr.
7.Head up to 100meters.
8.Operating pressure: Max.1.0~1.6 Mpa.
2.Water priming device
2.1 Outfit: Water storage tank for priming water, drain pipes for overflowing water, water-stopping cock with removal of remaining water, makeup water inlet connector(floating ball valve included), alarm device for low water level, auto water makeup device(check valve and water-stop clock included).
2.2 Storage tank is made of steel plate while its capacity of effective storage volume is above 100L.
2.3 Piping diameter of water supply pipes: 15A, drain pipes for water overflowing: 50A, water priming pipe: 40A.
2.4 Alarm device for low water level: Applied the floating ball switch or the electrode method; the alarm will be triggeredwhen the water level in water storage tank has been dropped to ½ capacity.
3.Thermal protector device
3.1 The discharging pipe for preventing the temperature rise of water is connected to the primary side of check
valve to the discharging side of water pump with an orifice plate mounted in between them so that the pump
can discharge minor volume of water into the room-temperature water storage tank during its operation.
3.2 There shall be no valves with a diameter bigger than 15A mounted to the piping of discharging pipes for preventing
the temperature rise of water.
3.3 The water volume flowing inside the discharging pipe for preventing the temperature rise of water is able to prevent
the water temperature inside the water pump from going higher than 30℃ when pump is at fully-shut status and
continuous running condition.
4.Test device for flow rate and performance
4.1 Able to test the pump water capacity during regular check.
4.2 Flowway flowmeter to measure and read directly the rated water volume and the range of 150% rated flow.
4.3 Mounted a pressure gauge with a precision above 1.5 class.
5.Main piping
5.1 If required Head is over 100M: ductile Iron silent check valve , ductile Iron Gate valve, Other connecting piping,20K flanges.
5.2 If required Head is below 100M: cast Iron silent check valve, cast Iron gate valve, other connecting piping,10K flanges.
6.Control panel
6.1 Indicators: power supply indicator, start indicator, water-reducing indicator of priming tank, overload indicator,automatic isolation indicator.
6.2 Operation switches: stop push button switch, start push button switch, reset switch, auto/stop/manual selection switch.
6.3 Alarm devices: alarm buzzers for overload of electric motor and water reduction of priming tank; manual and direct operation is needed to stop buzzing and reset the buzzer; motor will not stop automatically when alarm buzzer is triggered.
6.4 Instrument: ammeter and voltmeter.
6.5 Terminals: input terminal for start, input terminal for detecting the water reduction in priming tank, output terminal for alarm signal, output terminal for pump’s running signal, terminal for grounding. No-fuse breaker, electromagnetic switch,thermal relay.
7.Pressure Tank
7.1 Standard capacity of pressure tank is 100L,the maximum working pressure is 2.0Mpa.
7.2 Equipped with pressure gauge, pressure switch ,bronze gate valve, safety valve.
8.Pressure gauge and vacuum meter
8.1 Pressure gauge and vacuum meter with a precision above 1.5 Level.
9.Electric Motor (Diesel engine is optional per request)
9.1 Output ranges:5.5~75KW (Above 75KW output specifications are available upon special request).
9.2 Voltage/HZ: Three phase 220V/440V;380/660V/60HZ.
9.3 IP54;Insulation E,B,F; Enclosed Fan cooled induction motor(IEC standard).
9.4 Pole/RPM: 2P~4P/3500rpm~1750rpm.
10.Jockey Pump (Optional)
10.1 Vertical multi-stage centrifugal pump is designed for fire jockey pump.
10.2 Output range: 1.5~11KW ; Rated head:38~200M; Capacity:100~200L/min.
Fire Pump+Jockey Pump Installation
The purpose of installing fire jockey pump: When there is a leak in the fire pipe or sprinkler head, or when a small amount of water is consumed, the jockey pump will automatically boost the water first, without using the main pump. The main reason is that the main pump current and the water output are large. If there is a leak in the pipeline or sprinkler head, but no jockey pump is installed, the main pump must be automatically pressurized to supply water every time. Because of its large water output, the leakage point will be filled quickly, which may cause the fire main pump to on/off frequently. If water leakage in pipeline is not eliminated, the life of the unit will be affected. Generally speaking, the starting pressure set by the jockey pump will be higher than that of the main pump (about 0.5~1bar more). The matching horsepower of the jockey pump is also smaller than that of the main pump (about 10% of the main pump horsepower). Fire jockey pumps are often configured with fire sprinkler pumps. If the horsepower requirement of the fire pump is large or the fire pipeline extends for a long time, it is also recommended to add a fire jockey pump. (Remarks: There are three main types of EVERGUSH brand fire Jockey Pumps: WZ horizontal multi-stage pump / HDP high-pressure boiler pump / ECDL vertical multi-stage pump).
ON-SITE INSTALLATION
A.Installed in the basement machine room of the building or the machine room in the factory.
B.Dedicated to super high-rise buildings, installed in the machine room in the middle section of the high-rise building.
Notes : The pictures are for reference only. The quantity, purpose and specifications of fire pumps are configured according to actual site conditions
Installation
Working Conditions
- Ambient temperature: Max.40℃
- Liquid temperature: 0~60℃
- It is suitable for clean water or non chemical property liquid. It should not contain solid particles in the liquid.
- Working pressure: 10~20 Bar (Different water pumps withstand different pressure resistance.)
Specification
- Horsepower: 7.5HP~300HP
- Protection: IP54~55
- Insulation: B,F
- R.P.M: 2P,4P
- Voltage: 3 phase 220/380/440/660*60Hz
3 phase 380~415V*50Hz - Discharge/suction diameter: 21/2”~10”
- Head: Max. 230 M
- Capacity: 18~830M³/hr.